| Heat
Recovery
Heat recovery can be achieved in a
number of ways subject to applications.
Some typical examples are:
- Recuperators operate
in a similar way to plate heat exchangers,
by passing the air being extracted
from a building across one side
of the plate and the incoming air
over the other side of the plate,
the temperature difference during
cold outside conditions will allow
a transfer of heat into the cold
incoming air. A series of these
types of plates assembled together
will form a recuperator and is commonly
used in all types of ventilation
systems.
- Run-around Coils
are often used in air handling units
(AHU’s). A fluid, generally
a glycol mixture is circulated via
a pump set, through a coil situated
in the exhaust air path of the AHU.
This picks up the latent heat that
would otherwise be thrown out to
atmosphere. The heat is then transferred
into the working fluid and given
up into the cooler supply air path
of the AHU via another coil.
There are many situations
where in the region of 55% to 60%
of wasted heat can be recovered.
Optimisation
Conventional time control requires
a warm up period to be allowed at
the commencement of each heating period.
The warm up period would normally
be set to make allowance for the worst
winter conditions. This means that
during milder weather the system would
start much earlier than necessary
and therefore waste energy. The optimum
start monitors the actual warm up
period and also the degradation of
temperature after the system has switched
off.
By building up this data
the optimum start can calculate the
actual period required to bring the
area up to the required temperature
by the time required. This method
is accepted to make a saving of approximately
50% of the traditional warm up period
i.e. if a system without optimum start
would normally have a one hour warm
up period allowed then the average
saving over the heating season would
be 0.5 hours per day. An 8 hour day
plus the normal one hour warm up would
be 9 hours. A saving of an average
of 0.5 hours per day would therefore
represent in the region of 5.5% fuel
saving over a heating season compared
to a conventional time and temperature
control system.
Zone Control
Zone control is essential where a
building is divided into a number
of areas each with independent time
and temperature requirements. A well
designed zone control system would
have boiler interlock so that when
all zones are either up to temperature
or outside their timed on period the
boiler plant would switch off until
there is a demand on one of the zones.
Each zone can also have independent
optimum start as described above.
The combination of these
items in a well designed zone control
system will have a significant reduction
in running costs as well as minimising
carbon emissions to atmosphere.
When installing a zone
control system onto an existing heating
installation it is essential that
it is designed with a full knowledge
of the various types of system to
ensure that the zone valves are installed
in the correct position and any additional
modifications to pipework are carried
out to allow the valves to provide
the required function.
|